Arc Flash Protection Benefits

Image
The first post in this series covered a new arc flash related standard, the 2018 edition of NFPA 70E . It has some changes, such as allowing the use of a permanently mounted test equipment, that will make life easier. What is not changing are the benefits of arc flash protection. In an arc flash, current goes where it is not intended. It may jump from one conductor to another. Alternatively, current may jump from a conductor to ground. For either of these to happen in switchgear, typically the dielectric breakdown strength of air must be exceeded, or about 3 kV/mm of air gap. This means that an arc across a centimeter might take tens of kilovolts. The actual value might be a tenth that because the shape of the arcing electrode influences the breakdown voltage. A rounded arc launch point will have a higher breakdown than a pointy one. Another factor that may lower the breakdown value is the insertion of a foreign object, like a metal tool, into the gap. If the arc path is through m...